Calcium sulphate raised access floor with anti-static HPL finish
P-EC anti-static calcium sulphate panel consists of high strength calcium sulphate board and laminate with static dissipative HPL or PVC vinyl tile. The panel bottom is galvanized steel sheet, and four sides with PVC band edge, which prevents damages.
Fire resistance thermal principle: Non-combustible is a safety factor to stop fire from burning through the access floor. However, it doesn’t mean covering complete protection in terms of safety. The under-floor cavity provides space running pipes, cables, air-distribution, and tec. But in the meantime, it might become chamber of flame in case fire spreads underneath. The beat occurred at the bottom of panel can be effectively retarded by the panel core.
Features:
*High strength to weight performance, good fire-proof;
*Excellent anti-static performance
*Adjustable of finish floor height;
*Big space under the floor for electrical and plumbing facilities;
*Excellent sound and thermal insulation;
*Environment protecting;
*Convenient, high efficiency, flexible.
Specifications:
Type | Size(mm) | Concentrated Load(N/KG) | Rolling Load(N) | Ultimated Load(N) | Uniform Load(N/M2) | Fire protection performance | System resistancce |
P-EC 1000 | 600×600×30 | 4450/454 | 3560 | 13350 | 23000 | Non-conbustible Material | Anti-static floor system resistance 106~1010Ω |
P-EC 1250 | 600×600×32 | 5560/567 | 4450 | 16680 | 33000 |
With reference to National Standards and US CISCA test Standards